Tankless Water Heater Size Calculator
Use this free tankless water heater size calculator to find the electric (kW) or gas (BTU per hour) capacity you need. Add the hot water fixtures you run at the same time, set your incoming and desired water temperatures, and get the flow, temperature rise and size to buy. Want to see how winter changes the answer? Jump to why winter changes the size you need. Quick answer: size for the flow (GPM) of fixtures used together and the coldest incoming water. At the U.S. Department of Energy’s 50°F in and 120°F out (a 70°F rise), 3 GPM needs about 105,000 BTU/h of gas output or 30.8 kW of electric power.
Enter how many hot water fixtures you will run at the same time, then the water temperatures. The calculator gives the flow (GPM), the temperature rise, and the size to look for in kW (electric) or BTU per hour (gas).
| Fixture | How Many at Once | GPM Each | Subtotal |
|---|---|---|---|
| Shower (standard showerhead) | — | ||
| Bathroom sink | — | ||
| Kitchen sink | — | ||
| Dishwasher | — | ||
| Clothes washer | — | ||
| Large tub filler | — | ||
| — |
Temperature rise (°F) = Desired temperature − Incoming temperature
Electric size (kW) = GPM × Rise ÷ 6.83
Gas output (BTU/h) = 500 × GPM × Rise; gas input = Output ÷ Efficiency
Already Have a Heater in Mind? Check It
Enter the heater’s rating to compare it with your flow and temperature rise.
Size for the coldest incoming water of the year if the heater runs year-round, and for the most hot water you will realistically use at once. A heater is rated by the temperature rise it can deliver at a given flow, so a higher flow or a colder supply means a larger unit. Round up to the next available model.
Fixture flow rates and incoming temperatures vary. Measure your own fixtures if you can (time how long a bucket takes to fill) and check your local water temperature. Confirm the final choice with the manufacturer’s sizing chart and a licensed plumber or electrician.
Why Winter Changes the Size You Need
A tankless heater adds a fixed amount of heat to flowing water, so colder supply water means a bigger temperature rise at the same flow. SupplyHouse advises sizing on the coldest incoming water if the heater will be used year-round. The DOE suggests assuming 50°F incoming water unless you know otherwise, with a 120°F target (a 70°F rise).
Same Flow, Different Season (3 GPM to 120°F)
| Incoming Water | Temperature Rise | Electric Size | Gas Output |
|---|---|---|---|
| 35°F | 85°F | 37.3 kW | 127,500 BTU/h |
| 40°F | 80°F | 35.1 kW | 120,000 BTU/h |
| 50°F | 70°F | 30.7 kW | 105,000 BTU/h |
| 60°F | 60°F | 26.4 kW | 90,000 BTU/h |
| 70°F | 50°F | 22.0 kW | 75,000 BTU/h |
Going from 50°F to 40°F incoming water adds about 14% to the power needed for the same flow. A heater that was fine in summer can run short of hot water in winter, which is the point of sizing for the coldest month.
Typical Incoming Water Temperatures
- Cold northern climates: 35–50°F
- Mixed or temperate climates: 50–60°F
- Warm southern climates: 60–75°F
These ranges are from MEP Academy. Your actual supply temperature depends on pipe depth and the season; if you are unsure, use the lower end of your range. Insulating exposed water lines helps in winter; see our Pipe Insulation Calculator.
Electric vs. Gas Tankless Size
Electric Tankless Water Heater Size
Electric units are sized in kilowatts: kW = GPM × temperature rise ÷ 6.83, the formula Eemax prints. Whole-house units draw a lot of current. MEP Academy notes they may require multiple 40–60 A double-pole breakers and heavy conductors, so check your electrical service before choosing. Our Electrical Load Calculator and Electrical Panel Upgrade Cost Calculator can help.
Gas and Natural Gas Tankless Water Heater Size
Gas units are sized in BTU per hour: BTU/h ≈ 500 × GPM × temperature rise, where the 500 comes from the weight of water and the conversion from minutes to hours. The input rating is higher than the output because no heater is 100% efficient, so divide by the efficiency. MEP Academy says most residential gas tankless units are in the 150,000–199,000 BTU/h range. Natural gas and propane units use the same method; ask a licensed plumber or gas fitter to confirm gas line size and venting.
What the DOE Says About Capacity
The U.S. Department of Energy notes that tankless heaters are rated by the maximum temperature rise possible at a given flow, and that a 70°F rise is possible at about 5 gallons per minute for gas-fired units and about 2 gallons per minute for electric units. That is why a large household often needs a gas unit, more than one unit, or lower-flow fixtures.
Low-flow fixtures lower the required flow rate, and spreading out showers, the dishwasher and laundry lowers the peak. Both can let you choose a smaller, cheaper unit. For replacement costs, see our Water Heater Replacement Cost Calculator.
Quick Size Charts
Electric Size (kW) by Flow and Temperature Rise
| Flow | 40°F Rise | 50°F Rise | 60°F Rise | 70°F Rise | 80°F Rise | 90°F Rise |
|---|---|---|---|---|---|---|
| 2 GPM | 11.7 | 14.6 | 17.6 | 20.5 | 23.4 | 26.4 |
| 3 GPM | 17.6 | 22.0 | 26.4 | 30.7 | 35.1 | 39.5 |
| 4 GPM | 23.4 | 29.3 | 35.1 | 41.0 | 46.9 | 52.7 |
| 5 GPM | 29.3 | 36.6 | 43.9 | 51.2 | 58.6 | 65.9 |
| 6 GPM | 35.1 | 43.9 | 52.7 | 61.5 | 70.3 | 79.1 |
| 8 GPM | 46.9 | 58.6 | 70.3 | 82.0 | 93.7 | 105.4 |
Gas Output (BTU/h) by Flow and Temperature Rise
| Flow | 40°F Rise | 50°F Rise | 60°F Rise | 70°F Rise | 80°F Rise | 90°F Rise |
|---|---|---|---|---|---|---|
| 2 GPM | 40,000 | 50,000 | 60,000 | 70,000 | 80,000 | 90,000 |
| 3 GPM | 60,000 | 75,000 | 90,000 | 105,000 | 120,000 | 135,000 |
| 4 GPM | 80,000 | 100,000 | 120,000 | 140,000 | 160,000 | 180,000 |
| 5 GPM | 100,000 | 125,000 | 150,000 | 175,000 | 200,000 | 225,000 |
| 6 GPM | 120,000 | 150,000 | 180,000 | 210,000 | 240,000 | 270,000 |
| 8 GPM | 160,000 | 200,000 | 240,000 | 280,000 | 320,000 | 360,000 |
Temperature rise = desired temperature − incoming temperature. A 120°F target with 50°F incoming water is a 70°F rise. The DOE notes that a dishwasher without an internal heater may need 140°F water (a 90°F rise), and warns about the scalding risk at 140°F.
Typical Fixture Flow Rates
| Fixture | Typical Flow (GPM) | Source |
|---|---|---|
| Shower | 2.0–2.5 (standard 1.5–2.5; water-saving 1.2–1.8) | Eemax; MEP Academy; DOE example 2.5 |
| Bathroom sink | 0.5–1.5 | MEP Academy; Eemax 0.5 |
| Kitchen sink | 1.5–2.2 | MEP Academy; Eemax 2.0; DOE 2.0 for hand dishwashing |
| Dishwasher | 1.0–2.0 | Eemax; MEP Academy |
| Clothes washer | 1.0–3.0 | Eemax 1.0–1.5; MEP Academy 1.5–3.0 |
| Large tub filler | 4.0–6.0 or more | MEP Academy |
The calculator uses a single value from each range (shower 2.5, bathroom sink 0.5, kitchen sink 2.0, dishwasher 1.5, clothes washer 1.5, tub filler 4.0). Edit any value to match your fixtures. If you do not know a fixture’s flow, the DOE suggests holding a pan or bucket under it for one minute to measure.
Worked Examples
Example 1 — One Bathroom (Eemax’s Example)
Flow = 2.5 + 0.5 = 3 GPM; rise = 110 − 58 = 52°F
Electric size = 3 × 52 ÷ 6.83 = 22.8 kW (Eemax rounds the rise to 50°F and reads 22 kW from its chart)
Gas output = 500 × 3 × 52 = 78,000 BTU/h
Example 2 — The Calculator’s Defaults
Rise = 70°F; electric size = 3 × 70 ÷ 6.83 = 30.7 kW, which draws 128 A at 240 V
Gas output = 500 × 3 × 70 = 105,000 BTU/h; at 90% efficiency the input is 116,667 BTU/h
Example 3 — The Same House in Winter
Rise = 80°F; electric size = 3 × 80 ÷ 6.83 = 35.1 kW; gas output = 120,000 BTU/h
That is about 14% more than Example 2 for the same flow.
Example 4 — Two Showers and the Kitchen Sink
Flow = 7 GPM; gas output = 500 × 7 × 70 = 245,000 BTU/h; input at 90% = 272,222 BTU/h
That is more than the 150,000–199,000 BTU/h that most residential gas units provide, so you would need two units, fewer fixtures at once, or lower-flow fixtures. Electric size would be 71.7 kW, which is a very large electrical load.
Example 5 — Can a 199,000 BTU/h Gas Heater Cope?
At a 70°F rise: 179,100 ÷ (500 × 70) = 5.1 GPM
At an 80°F winter rise: 179,100 ÷ (500 × 80) = 4.5 GPM. It can serve the 3 GPM household, but not the 7 GPM case in Example 4.
Common Mistakes When Sizing a Tankless Water Heater
- Sizing on summer water temperature. Use the coldest incoming water of the year.
- Counting fixtures instead of simultaneous flow. Add only what will run together.
- Mixing up input and output. A gas heater’s input BTU/h is higher than the heat it delivers.
- Forgetting the electrical load. Whole-house electric units may need multiple large breakers and heavy wiring.
- Setting the temperature too high. Most uses need about 120°F; the DOE warns about scalding at 140°F.
- Ignoring the dishwasher. One without an internal heater may need hotter water.
- Trusting default flow rates. Measure your own fixtures if you can.
- Skipping gas line and venting checks on a gas replacement; larger input needs adequate supply and venting.
How We Calculate
Flow. The sum of count × GPM for every fixture you will run at the same time.
Temperature rise. Desired temperature − incoming temperature. The default incoming temperature of 50°F and the 120°F target follow the U.S. Department of Energy’s sizing guidance.
Electric size. kW = GPM × rise ÷ 6.83, from Eemax. The constant is 3,412 Btu per kWh divided by the 500 factor, so it assumes essentially all electricity becomes heat. Current = kW × 1,000 ÷ 240 V.
Gas size. Output BTU/h = 500 × GPM × rise, the formula given by MEP Academy. Input BTU/h = Output ÷ Efficiency. The 90% default is our planning value; use the efficiency on your heater’s rating plate.
Heater check. Maximum flow = Delivered heat ÷ (500 × rise) for gas, or kW × 6.83 ÷ rise for electric. Delivered heat for gas = Input × Efficiency.
Limits. This is a planning estimate. Real units vary in their rated flow at each rise, and water pressure, pipe length and fixture mix affect performance. Use the manufacturer’s sizing chart for the final choice.
We use AI tools to help draft and format some content. The figures on this page come from the published sources listed below, and the formulas and examples were checked before publication. See our editorial policy.
Frequently Asked Questions
Plan your water heating and winter home projects with these free tools.
Water Heating & Plumbing
Electrical & Backup Power
Sources and References
The figures on this page were checked against the sources below in October 2026.
- U.S. Department of Energy — Sizing a New Water Heater: tankless heaters rated by temperature rise at a flow rate, the 50°F incoming and 120°F target assumptions, 140°F for dishwashers without internal heaters, the scalding warning, and the 2 GPM electric / 5 GPM gas figures at a 70°F rise.
- Eemax — Simple Formula Ensures Proper Size of Tankless Electric Water Heater: the kW = GPM × rise ÷ 6.83 formula, typical GPM requirements and the one-bathroom worked example.
- MEP Academy — How to Size Tankless Water Heaters: fixture flow ranges, the BTU/h ≈ 500 × GPM × rise formula, incoming water temperature ranges by climate, gas input range and electric breaker notes.
- SupplyHouse — How to Size a Tankless Water Heater: showers at 2–2.5 GPM and sizing for the coldest incoming water of the year.
Heater ratings vary by manufacturer and model, so use the manufacturer’s sizing chart and a licensed plumber or electrician for the final choice. ConstructlyTools has no paid relationship with any manufacturer or retailer mentioned.
Prakash
Prakash is the founder and editor of ConstructlyTools. He researches, develops, and maintains construction calculators, material estimators, cost guides, and DIY planning resources designed to help homeowners, contractors, and builders make informed project decisions.
Every calculator and guide is researched using trusted industry references, published building standards, manufacturer specifications, and reliable construction pricing sources. Each page is reviewed for formula accuracy, pricing methodology, readability, and practical usefulness before publication and is updated regularly as standards or market prices change.
Every calculator and article published on ConstructlyTools is reviewed by the editor for formula accuracy, pricing methodology, readability, and practical usefulness before publication. We use AI tools to help draft and format some content; every figure and formula is checked by the editor before publication. Content is updated whenever construction pricing, industry standards, or building code references significantly change.
This page was researched, written, and reviewed in accordance with our Editorial Policy.